Proline Promag W 500 PROFINET
Electrical connection
Hauser
47
7.1.4
Device plugs available
Device plugs may not be used in hazardous areas!
Order code for "Input; output 1", option RA "PROFINET"
Order code for
Cable entry/connection
"Electrical connection"
2
3
L, N, P, U
Connector M12 × 1
–
R
, T
Connector M12 × 1
Connector M12 × 1
1)
Cannot be combined with an external WLAN antenna (order code for "Enclosed accessories", option P8) of
an RJ45 M12 adapter for the service interface (order code for "Accessories mounted", option NB) or of the
remote display and operating module DKX001.
2)
Suitable for integrating the device in a ring topology.
7.1.5
Pin assignment of device plug
3
2
4
1
A0032047
Pin
Assignment
1
+
TD +
2
+
RD +
3
-
TD –
4
-
RD –
Coding
Plug/socket
D
Socket
7.1.6
Preparing the measuring device
Carry out the steps in the following order:
1. Mount the sensor and transmitter.
2. Connection housing, sensor: Connect connecting cable.
3. Transmitter: Connect connecting cable.
4. Transmitter: Connect signal cable and cable for supply voltage.
NOTICE
Insufficient sealing of the housing!
Operational reliability of the measuring device could be compromised.
‣
Use suitable cable glands corresponding to the degree of protection.
1. Remove dummy plug if present.
2. If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3. If the measuring device is supplied with cable glands:
Содержание Proline Promag W 500
Страница 262: ...www addresses endress com...