Installation
6.1
Installation conditions
6.1.1
Mounting position
Mounting location
h
A0029343
Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the
next pipe elbow: h ≥ 2 × DN
Not necessary for the order code for "Design", option C
1
1
A0033017
6
Installation of the sensor after a control valve is not recommended
1
Control valve
Installation in down pipes
Install a siphon with a vent valve downstream of the sensor in down pipes whose length h
≥ 5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of
damage to the measuring tube. This measure also prevents the system losing prime.
h
2
1
A0028981
7
Installation in a down pipe
1
Vent valve
2
Pipe siphon
h
Length of down pipe