Operation
Proline Promag W 500 PROFINET
168
Hauser
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry / User
interface
Factory setting
Assign channel 1
The
Extended HistoROM
application package is
available.
Assign process variable to
logging channel.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Electronic
temperature
• Current output 1
• Current output 2
• Current output 3
• Current output 4
• Noise
• Coil current shot
time
• Reference
electrode potential
against PE
• Coating measured
value
• Test point 1
• Test point 2
• Test point 3
Off
Assign channel 2
The
Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview
parameter.
Assign process variable to
logging channel.
Picklist, see
Assign
channel 1
parameter
Off
Assign channel 3
The
Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview
parameter.
Assign process variable to
logging channel.
Picklist, see
Assign
channel 1
parameter
Off
Assign channel 4
The
Extended HistoROM
application package is
available.
The software options
currently enabled are
displayed in the
Software option
overview
parameter.
Assign process variable to
logging channel.
Picklist, see
Assign
channel 1
parameter
Off
Logging interval
The
Extended HistoROM
application package is
available.
Define the logging interval for
data logging. This value
defines the time interval
between the individual data
points in the memory.
0.1 to 3
600.0 s
1.0 s
Clear logging data
The
Extended HistoROM
application package is
available.
Clear the entire logging data.
• Cancel
• Clear data
Cancel
Data logging
–
Select the data logging
method.
• Overwriting
• Not overwriting
Overwriting
Содержание Proline Promag W 500