Electrical connection
Proline Promag W 500 PROFINET
46
Hauser
1
2
3
4
5
6
7
a
b
A0029151
16
Cable cross-section
a
Electrode cable
b
Coil current cable
1
Core
2
Core insulation
3
Core shield
4
Core jacket
5
Core reinforcement
6
Cable shield
7
Outer jacket
Reinforced connecting cables
Reinforced connecting cables with an additional, reinforcing metal braid should be used
for:
• When laying the cable directly in the ground
• Where there is a risk of damage from rodents
• If using the device below IP68 degree of protection
Operation in zones of severe electrical interference
The measuring system meets the general safety requirements → 252 and EMC
specifications → 236.
Grounding is by means of the ground terminal provided for the purpose inside the
connection housing. The stripped and twisted lengths of cable shield to the ground
terminal must be as short as possible.
7.1.3
Terminal assignment
Transmitter: supply voltage, input/outputs
The terminal assignment of the inputs and outputs depends on the individual order
version of the device. The device-specific terminal assignment is documented on an
adhesive label in the terminal cover.
Supply voltage
Input/output
1
Input/output
2
Input/output
3
Input/output
4
1 (+)
2 (–)
PROFINET
(RJ45 connector)
24 (+)
25 (–)
22 (+)
23 (–)
20 (+)
21 (–)
Device-specific terminal assignment: adhesive label in terminal
cover.
Transmitter and sensor connection housing: connecting cable
The sensor and transmitter, which are mounted in separate locations, are interconnected
by a connecting cable. The cable is connected via the sensor connection housing and the
transmitter housing.
Terminal assignment and connection of the connecting cable: