5. Install the measuring device or turn the transmitter housing so that the cable entries
do not point upwards.
A0029263
Mounting the seals
L
CAUTION
An electrically conductive layer could form on the inside of the measuring tube!
Risk of measuring signal short circuit.
‣
Do not use electrically conductive sealing compounds such as graphite.
Comply with the following instructions when installing seals:
1. Make sure that the seals do not protrude into the piping cross-section.
2. For DIN flanges: only use seals according to DIN EN 1514-1.
3. For "hard rubber" liner: additional seals are
always
required.
4. For "polyurethane" liner: generally additional seals are
not
required.
Mounting the ground cable/ground disks
Comply with the information on potential equalization and detailed mounting instructions
for the use of ground cables/ground disks → 65.
Screw tightening torques
Please note the following:
• The screw tightening torques listed below apply only to lubricated threads and to pipes
not subjected to tensile stress.
• Tighten the screws uniformly and in diagonally opposite sequence.
• Overtightening the screws will deform the sealing faces or damage the seals.
Nominal screw tightening torques → 35
Maximum screw tightening torques
Maximum screw tightening torques for EN 1092-1 (DIN 2501)
Nominal diameter
Pressure
rating
Screws
Flange
thickness
Max. screw tightening torque [Nm]
[mm]
[in]
[bar]
[mm]
[mm]
HG
PUR
PTFE
25
1
PN 40
4 × M12
18
–
15
26
32
–
PN 40
4 × M16
18
–
24
41
40
1 ½
PN 40
4 × M16
18
–
31
52
50
2
PN 40
4 × M16
20
48
40
65
65
–
PN 16
8 × M16
18
32
27
44
65
–
PN 40
8 × M16
22
32
27
44
80
3
PN 16
8 × M16
20
40
34
53
PN 40
8 × M16
24
40
34
53
Содержание Proline Promag W 500