Proline Promag W 500 PROFINET
System integration
Hauser
105
9.3
Cyclic data transmission
9.3.1
Overview of the modules
The following tables shows which modules are available to the measuring device for cyclic
data exchange. Cyclic data exchange is performed with an automation system.
Measuring device
Direction
Data flow
Control system
Module
Slot
Analog Input module → 105
1…10, 18…20
→
PROFINET
Digital Input module → 106
1…10
→
Diagnose Input module → 106
1…10
→
Analog Output module → 108
14, 15
←
Digital Output module → 110
16, 18…20
←
Totalizer 1 to 3 → 107
11…13
←
→
Heartbeat Verification module → 110
17
←
→
9.3.2
Description of the modules
The data structure is described from the perspective of the automation system:
• Input data: Are sent from the measuring device to the automation system.
• Output data: Are sent from the automation system to the measuring device.
Analog Input module
Transmit input variables from the measuring device to the automation system.
Analog Input modules cyclically transmit the selected input variables, along with the
status, from the measuring device to the automation system. The input variable is depicted
in the first four bytes in the form of a floating point number as per the IEEE 754 standard.
The fifth byte contains status information pertaining to the input variable.
Selection: input variable
Slot
Input variables
1…10
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronics temperature
• Noise
• Coil current rise time
• Reference electrode potential against PE
18 to 20
Current input value