Proline Promag W 500 PROFINET
Commissioning
Hauser
123
Failure mode
Failure current
Parameter overview with brief description
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Terminal number
–
Shows the terminal numbers
used by the current output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Signal mode
–
Select the signal mode for the
current output.
• Active
• Passive
Active
Assign current output 1 to n
–
Select process variable for
current output.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Electronic
temperature
• Reference
electrode potential
against PE
• Coil current shot
time
• Noise
• Coating measured
value
• Test point 1
• Test point 2
• Test point 3
Volume flow
Current span
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed current
Country-specific:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
0/4 mA value
In the
Current span
parameter
(→ 123), one of the
following options is selected:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter 4 mA value.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
20 mA value
One of the following options is
selected in the
Current span
parameter (→ 123):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Enter 20 mA value.
Signed floating-point
number
Depends on country
and nominal
diameter