Proline Promag W 500 PROFINET
Technical data
Hauser
221
16
Technical data
16.1 Application
The measuring device is only suitable for flow measurement of liquids with a minimum
conductivity of 5 µS/cm.
Depending on the version ordered, the measuring device can also measure potentially
explosive, flammable, poisonous and oxidizing media.
To ensure that the device remains in proper operating condition for its service life, use the
measuring device only for media against which the process-wetted materials are
sufficiently resistant.
16.2 Function and system design
Measuring principle
Electromagnetic flow measurement on the basis of
Faraday's law of magnetic induction
.
Measuring system
The measuring system consists of a transmitter and a sensor. The transmitter and sensor
are mounted in physically separate locations. They are interconnected by connecting
cables.
For information on the structure of the device → 14
16.3 Input
Measured variable
Direct measured variables
• Volume flow (proportional to induced voltage)
• Electrical conductivity
Calculated measured variables
• Mass flow
• Corrected volume flow
Measuring range
Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Electrical conductivity: ≥ 5 μS/cm for liquids in general
Flow characteristic values in SI units: DN 25 to 125 (1 to 4")
Nominal diameter
Recommended
flow
Factory settings
min./max. full
scale value
(v ~ 0.3/10 m/s)
Full scale value
current output
(v ~ 2.5 m/s)
Pulse value
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
[mm]
[in]
[dm
3
/min]
[dm
3
/min]
[dm
3
]
[dm
3
/min]
25
1
9 to 300
75
0.5
1
32
–
15 to 500
125
1
2
40
1 ½
25 to 700
200
1.5
3
50
2
35 to 1
100
300
2.5
5
65
–
60 to 2
000
500
5
8