Proline Promag W 500 PROFINET
Diagnostics and troubleshooting
Hauser
175
LED
Color
Meaning
Flashing green
Device is not configured.
Flashing red
A diagnostic event with "Warning" diagnostic
behavior has occurred.
Red
A diagnostic event with "Alarm" diagnostic behavior
has occurred.
Flashing red/green
The device restarts.
2
Device status (during
start-up)
Flashes red slowly
If > 30 seconds: problem with the boot loader.
Flashes red quickly
If > 30 seconds: compatibility problem when
reading the firmware.
3
Flashing/network status Green
Cyclic data exchange is active.
Flashing green
Following request from automation system:
Flash frequency: 1 Hz (flash functionality: 500 ms
on, 500 ms off)
Cyclic data exchange is not active, no IP address is
available:
Flash frequency: 3 Hz
Red
IP address is available but there is no connection to
the automation system
Flashing red
Cyclic data exchange was active but the connection
was disconnected:
Flash frequency: 3 Hz
4
Port 1 active:
PROFINET
Off
Not connected or no connection established.
White
Connected and connection established.
Flashing white
Communication not active.
5
Port 2 active:
PROFINET and
service interface (CDI)
Off
Not connected or no connection established.
Yellow
Connected and connection established.
Flashing yellow
Communication not active.
12.2.2 Sensor connection housing
Proline 500 – digital
Various light emitting diodes (LED) on the ISEM electronics (Intelligent Sensor Electronic
Module) in the sensor connection housing provide information on the device status.
64
63
61
62
A
B
L-
L+
Communication
Power
Communication
Alarm
Power
1
2
3
A0029699
1
Communication
2
Device status
3
Supply voltage