Proline Promag W 500 PROFINET
Diagnostics and troubleshooting
Hauser
195
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
376 Sensor electronic (ISEM) faulty
1. Replace sensor electronic module
(ISEM)
2. Turn off diagnostic message
• Conductivity
• Corrected conductivity
• Measured values 1
• Measured values 2
• Measured values 3
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status [from the factory]
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
377 Sensor electronic (ISEM) faulty
1. Activate empty pipe detection
2. Check partial filled pipe and installation
direction
3. Check sensor cabling
4. Deactivate diagnostic 377
• Conductivity
• Corrected conductivity
• Density
• Electronic temperature
• Flow velocity
• Mass flow
• Coil current shot time
• Reference electrode
potential against PE
• Noise
• Reference density
• Corrected volume flow
• Temperature
• Status
• Volume flow
Measured variable status [from the factory]
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
378 Supply voltage ISEM faulty
Check supply voltage to the ISEM
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
F
Diagnostic behavior
Alarm