Proline Promag W 500 PROFINET
System integration
Hauser
109
Available units
Density
Temperature
Unit code
Unit
Unit code
Unit
1100
g/cm
3
1001
°C
1101
g/m
3
1002
°F
1099
kg/dm
3
1000
K
1103
kg/l
1003
°R
1097
kg/m
3
1628
SD4°C
1629
SD15°C
1630
SD20°C
32833
SG4°C
32832
SG15°C
32831
SG20°C
1107
lb/ft
3
1108
lb/gal (us)
32836
lb/bbl (us;liq.)
32835
lb/bbl (us;beer)
32837
lb/bbl (us;oil)
32834
lb/bbl (us;tank)
1403
lb/gal (imp)
32838
lb/bbl (imp;beer)
32839
lb/bbl (imp;oil)
Data structure
Output data of Analog Output
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Measured value: floating point number (IEEE 754)
Status
Unit code
1)
Status coding → 111
Failsafe mode
A failsafe mode can be defined for using the compensation values.
If the status is GOOD or UNCERTAIN, the compensation values transmitted by the
automation system are used. If the status is BAD, the failsafe mode is activated for the use
of the compensation values.
Parameters are available per compensation value to define the failsafe mode: Expert
→ Sensor → External compensation
Fail safe type parameter
• Fail safe value option: The value defined in the Fail safe value parameter is used.
• Fallback value option: The last valid value is used.
• Off option: The failsafe mode is disabled.
Fail safe value parameter
Use this parameter to enter the compensation value which is used if the Fail safe value
option is selected in the Fail safe type parameter.