Proline Promag W 500 PROFINET
Technical data
Hauser
229
Number of switching
cycles
Unlimited
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value:
• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Totalizer 1-3
• Electronics temperature
• Flow direction monitoring
• Status
• Empty pipe detection
• Low flow cut off
Relay output
Function
Switch output
Version
Relay output, galvanically isolated
Switching behavior
Can be set to:
• NO (normally open), factory setting
• NC (normally closed)
Maximum switching
capacity (passive)
• DC 30 V, 0.1 A
• AC 30 V, 0.5 A
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value:
• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Totalizer 1-3
• Electronic temperature
• Flow direction monitoring
• Status
• Empty pipe detection
• Low flow cut off
User-configurable input/output
One
specific input or output is assigned to a user-configurable input/output (configurable
I/O) during device commissioning.
The following inputs and outputs are available for assignment:
• Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Pulse/frequency/switch output
• Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
• Status input
Signal on alarm
Depending on the interface, failure information is displayed as follows:
PROFINET
Device diagnostics
According to "Application Layer protocol for decentralized periphery", Version 2.3