Proline Promag W 500 PROFINET
Commissioning
Hauser
119
10.5.4 Selecting and setting the medium
The
Select medium
wizard submenu contains parameters that must be configured in
order to select and set the medium.
Navigation
"Setup" menu → Select medium
‣
Medium selection
Select medium
Pressure compensation
Pressure value
External pressure
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Select medium
–
Select medium type.
• Liquid
• Gas
Liquid
Pressure compensation
–
Select pressure compensation
type.
• Off
• Fixed value
• External value
Off
Pressure value
The
Fixed value
option or the
Current input 1…n
option is
selected in the
Pressure
compensation
parameter.
Enter process pressure to be
used for pressure correction.
Positive floating-
point number
0 bar
External pressure
The
Fixed value
option or the
Current input 1…n
option is
selected in the
Pressure
compensation
parameter.
Positive floating-
point number
0 bar
10.5.5 Displaying the I/O configuration
The
I/O configuration
submenu guides the user systematically through all the parameters
in which the configuration of the I/O modules is displayed.
Navigation
"Setup" menu → I/O configuration
‣
I/O configuration
I/O module 1 to n terminal numbers
I/O module 1 to n information
I/O module 1 to n type
Содержание Proline Promag W 500