Commissioning
Proline Promag W 500 PROFINET
124
Hauser
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Fixed current
The
Fixed current
option is
selected in the
Current span
Defines the fixed output
current..
0 to 22.5 mA
22.5 mA
Damping output 1 to n
A process variable is selected
in the
Assign current output
parameter (→ 123) and
one of the following options is
selected in the
Current span
parameter (→ 123):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Set reaction time for output
signal to fluctuations in the
measured value.
0.0 to 999.9 s
1.0 s
Failure mode
A process variable is selected
in the
Assign current output
parameter (→ 123) and
one of the following options is
selected in the
Current span
parameter (→ 123):
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US (3.9...20.8
mA)
• 4...20 mA (4... 20.5 mA)
• 0...20 mA (0... 20.5 mA)
Define output behavior in
alarm condition.
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
Max.
Failure current
The
Defined value
option is
selected in the
Failure mode
parameter.
Enter current output value in
alarm condition.
0 to 22.5 mA
22.5 mA
*
Visibility depends on order options or device settings