Proline Promag W 500 PROFINET
Commissioning
Hauser
127
Minimum frequency value
Maximum frequency value
Measuring value at minimum
frequency
Measuring value at maximum
frequency
Failure mode
Failure frequency
Invert output signal
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
interface / User
entry
Factory setting
Operating mode
–
Define the output as a pulse,
frequency or switch output.
• Pulse
• Frequency
• Switch
Pulse
Terminal number
–
Shows the terminal numbers
used by the PFS output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Signal mode
–
Select the signal mode for the
PFS output.
• Passive
• Active
• Passive NAMUR
Passive
Assign frequency output
The
Frequency
option is
selected in the
Operating
mode
Select process variable for
frequency output.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Electronic
temperature
• Noise
• Coil current shot
time
• Reference
electrode potential
against PE
• Coating measured
value
• Test point 1
• Test point 2
• Test point 3
Off
Minimum frequency value
The
Frequency
option is
selected in the
Operating
mode
and a process variable is
selected in the
Assign
frequency output
parameter
Enter minimum frequency.
0.0 to 10
000.0 Hz
0.0 Hz