Proline Promag W 500 PROFINET
Installation
Hauser
25
Horizontal
• Ideally, the measuring electrode plane should be horizontal. This prevents brief
insulation of the two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as
otherwise there is no guarantee that the empty pipe detection function will actually
respond to a partially filled or empty measuring tube.
1
2
3
2
A0029344
1
EPD electrode for empty pipe detection
2
Measuring electrodes for signal detection
3
Reference electrode for potential equalization
Inlet and outlet runs
If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:
≥ 5 × DN
≥ 2 × DN
A0028997
For sensors with the order code for "Design", option C "Fixed flange, w/o inlet/outlet runs",
no inlet and outlet runs must be taken into account.
≥ 0 × DN
A0032859
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section.