Proline Promag W 500 PROFINET
Technical data
Hauser
231
Interface/protocol
• Via digital communication:
PROFINET
• Via service interface
• CDI-RJ45 service interface
• WLAN interface
Plain text display
With information on cause and remedial measures
Web browser
Plain text display
With information on cause and remedial measures
Light emitting diodes (LED)
Status information
Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
Diagnostic information via light emitting diodes → 173
Low flow cut off
The switch points for low flow cut off are user-selectable.
Galvanic isolation
The outputs are galvanically isolated from one another and from earth (PE).
Protocol-specific data
Protocol
Application layer protocol for decentral device periphery and distributed
automation, Version 2.3
Communication type
100 MBit/s
Conformity class
Conformance Class B
Netload Class
Netload Class II
Baud rates
Automatic 100 Mbit/s with full-duplex detection
Cycle times
From 8 ms
Polarity
Auto-polarity for automatic correction of crossed TxD and RxD pairs
Media Redundancy Protocol
(MRP)
Yes
System redundancy support
System redundancy S2 (2 AR with 1 NAP)
Device profile
Application interface identifier 0xF600
Generic device
Manufacturer ID
0x11
Device type ID
0x843C
Device description files (GSD,
DTM, DD)
Information and files under:
•
On the product page for the device: Documents/Software → Device drivers
•
www.profibus.org