5-9
Chapter 5. FUNCTIONS
However, ON and OFF times set for seg-
ment end points when the END mode is
shifted to are valid.
(See segment 9 in the figure, and com-
pare with segment 10 in the END mode.)
• When the ON time is set to 0 (no OFF
time setting, or OFF time is greater than
0), output becomes OFF at time 0.
If output at the previous segment end
point was ON at this time, the output
status at the segment switching point
does not momentarily become OFF.
(See segments 5 and 6 in the figure.)
• The G.Soak standby time is not included
in the ON and OFF times.
(See segment 7 in the figure.)
• If the ON time is set to 0 in the case of
G.Soak standby, output becomes ON
from the G.Soak standby state, and the
ON time is started at completion of the
G.Soak standby time.
The output time = G.Soak time + OFF
time
(See segment 8 in the figure.)
• ON and OFF time settings the same time
as the segment end point are valid in the
case of the final segment END mode.
(See segment 10 in the figure.)
Segment
5
6
ON time
OFF time
Output ON
Output OFF
ON
continued
G.Soak standby
ON=0
Segment
7
ON time
OFF time
Output ON
Output OFF
Segment time start
Segment
8
ON time
OFF time
Output ON
Output OFF
G.Soak standby
Segment
9
ON time
OFF time
Output ON
Output OFF
ON=segment time
Segment
10
Segment time
ON time
OFF time
Output ON
Output OFF
END mode
ON=segment time
Segment 8 time start
When 0N=0, output turns
ON when there is input to
segment 8.