7-12
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
31
.-c
l
Motor valve open-
ing adjustment fully
closed position
1000
0 to (fully open adjustment - 500)
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
On 2G output models, when
.-C
setting is 2, “– – – –”is displayed and
setting is not possible.
32
.-O
p
Motor valve open-
ing adjustment fully
open position
9000
(fully closed adju 500) to 9999
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
On 2G output models, when
.-C
setting is 2, “– – – –” is displayed and
setting is not possible.
33
.-t
Motor valve open-
ing adjustment fully
open/closed time
30.0
5.0 to 240.0 s
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
■
Description of variable parameter settings
●
●
L
O
C
(key lock)
0: Key lock disabled
1: Display of setup data settings disabled
2: Display of parameter settings and program settings disabled
3: Use of operation keys disabled
4: Display of parameter settings and program settings displayed,
and use of operation keys disabled
• When
L
O
C
is set to 1, the following keys are disabled.
Basic display state:
FUNC
+
CLR
+
DISP
(general reset)
Only
S
E
T
can be selected by setting group selection in the param-
eter setup state.
• When
L
O
C
is set to 2, the following keys are disabled.
Basic display state:
FUNC
+
PROG
(program setup)
+
PROG
(program copy)
FUNC
+
CLR
+
DISP
(general reset)
Only
P
A
R
A
can be selected by setting group selection in the
parameter setup state.
However, note that items assigned to
PARA
can be called up by
PARA
in the basic display state.