7-6
Chapter 7. PARAMETER SETUP
●
●
Example
Let’s register four individual items to
PARA
. If you press
PARA
in the
basic display state, the 1st to 4th individual items in the table below
are displayed successively. In this example, let’s change the setting
values.
Order
Item to Call by
PARA
1
Setup data
C
0
1
2
PID parameter
P
-2
3
Variable parameter
F
L
4
Variable parameter
F
A
S
T
The settings for registering these individual items are as follows:
Setup Data Setting “
S
E
t
”
No.
Item Code
[auxiliary
display]
Item
Setting
Value
Remarks
55
C
5
5
PARA
assignment
item 1
4501
This is produced by adding item No.1 of
C
0
1
to setup data radical 4500.
56
C
5
6
PARA
assignment
item 2
1511
This is produced by adding item No.11
of
P
-2
to PID parameter radical 1500.
57
C
5
7
PARA
assignment
item 3
2503
This is produced by adding item No.3
of
F
L
to setup data radical 2500.
58
C
5
8
PARA
assignment
item 4
2520
This is produced by adding item No.20
of
F
A
S
T
to variable parameter radical
2500.
Handling Precautions
• For details on item Nos., see 7-3 Parameter Setup List (pages 7-7
to 7-42).
• When the “
PARA
assignment item” setting is set to a value that
does not correspond to an existing item, that setting is ignored.
For example, though factory setting 1000 corresponds to “con-
stant-value operation data” 0th of base 1000, 0th does not exist,
so the setting will be treated an invalid data and will not be regis-
tered.