In the case of thermocouple input, connect the bare thermocouple lead to the terminal. If the
thermocouple is located a long way from the
DCP31
or the thermocouple is connected to a ter-
minal, extend the connection using a compensating lead and then connect to the terminal. Use
shielded compensating leads only.
• For I/O other than thermocouples, use JCS4364 instrument cable
or equivalent product. (This is generally referred to “twisted
shielded cable for instruments.”) The following cables are recom-
mended.
Fujikura Ltd.
2-core IPEV-S-0.9 mm
2
x 1P
3-core
ITEV-S-0.9 mm
2
x 1T
Hitachi Metals Ltd. 2-core
KPEV 0.9 mm
2
x 1P
3-core KTEV-S-0.9 mm
2
x 1T
• Shielded, multi-core microphone cord (MVVS) can be used if
there is little electromagnetic induction.
• Use a power supply cable with a nominal cross-sectional area
of 0.75 to 2.0 mm
2
, rated voltage of more than 300 V, and rated
temperature of more than 60 °C.
4-3
Chapter 4. WIRING
4 - 2
Compensating Lead