Safety Requirement
To reduce the risk of an electric shock resulting in personal injury, follow all safety no-
tices in this document.
This symbol warns the user when there is a danger of electric shock from accidental
contact.
• The use of this product in a manner not specified by the manufacturer will impair its built-in safety
features.
• Do not replace any component or part not explicitly specified as replaceable by the manufacturer.
• All wiring must be in accordance with local regulations and carried out by authorized and experi-
enced personnel.
• To be safe, be sure to wire the ground terminal before other wiring.
• Be sure to mount a switch for shutoff of the main power to this device within reach of the operator.
• Connect a time-lag fuse with a rated current of 1.0 A and rated voltage of 250 V to the wiring for the
device power supply. (Reference: IEC 127)
• The fuse must be connected to the wiring on the non-grounded side.
• If a fuse is needed, please use the following.
Manufacturer: Littelfuse, Inc.
Model No.: 218001
Rating:
250 Vac, 1 A
●
EQUIPMENT RATINGS
Supply voltage:
100 to 240 Vac (operating supply voltage: 90 to 264 Vac)
Frequency:
50/60 Hz
Power consumption: 30 VA max.
●
EQUIPMENT CONDITIONS
Do not use this device near flammable fluids or vapors. Under such circumstances, safety will be
impaired.
Operating temperature: 0 to 50 °C
Operating humidity:
10 to 90 %RH (without condensation)
Vibration:
1.96 m/s
2
max. (10 to 60 Hz for 2 h each in x, y, and z directions)
Overvoltage:
Category II (IEC 60364-4-443, IEC 60664-1)
Pollution degree:
2
Installation location:
Indoors
Altitude:
2000 m max.
●
EQUIPMENT INSTALLATION
• Be sure to mount this device in a panel so that operators do not touch the rear terminal block.
• With the exception of supply power and relay contact output, the I/O common mode voltage
with respect to the ground should be 33 VRMS max., 46.7 V peak max., and 70 Vdc max.
●
STANDARDS COMPLIANCE
EN61010-1,
EN61326-1 (For use in industrial locations)
During EMC testing, the reading or output may fluctuate by ± 10 % FS.
However, the MFB (motor-opening feedback) is within ± 30 % FS.
WARNING
There is a danger of explosion if the battery is incorrectly replaced.
When replacing the battery, use only the type specified in this user's manual or an equivalent type.
Dispose of used batteries according to the manufacturer's instructions.