Event outputs EV1 and EV2 are 1a contact, and event output EV3 is 1a1b. Event outputs are con-
nected on the standard terminal base.
Handling Precautions
• When switching small currents, connect a bleeder resistor to
allow current flow of the minimum relay switching input (10 mA
min.).
10
8
9
6
7
4
5
EV1 1a
EV2 1a
EV3 1a1b
Load
Power supply
Load
Power supply
Load
Power supply
Standard terminal base
Contact rating, resistive load
1A (30/250 Vdc)
Contact rating, resistive load
1A (30/250 Vdc)
Contact rating, resistive load
2A (30/250 Vdc)
Minimum switching current: 10 mA
4-13
Chapter 4. WIRING
4 - 10
Connecting Event Output (relay output)