7-45
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
5
C
0
5
Input 1 range lower
limit (0 %)
Not fixed
-1999 to +9999 U
[Note]
When the input 1 range type is non-
linear, “– – – –” is displayed and setting
is not possible.
When the input 1 range type is
changed from nonlinear to linear,
the original non-linear range values
remain.
The relationship between the analog
inputs and readout values can be
inverted by inverting the upper and
lower limit values.
6
C
0
6
Input 1 range upper
limit (100 %)
Not fixed
7
C
0
7
Input 1 root extrac-
tion dropout
0.0
0.0 to 10.0 % (ratio to input range)
[Note]
0.0 disables square root extraction.
When the input 1 range type is non-
linear, “– – – –” is displayed and setting
is not possible.
8
C
0
8
Input 1 linearization
table approximation
0
0: Disabled
1: Enabled
[Note]
Table data setting (
a
,
b
) is used for the
linearization table.
9
C
0
9
SP1 lower limit
0 %FS
-1999 to upper limit U
[Note]
Changing the input 1 range has no
effect on the range.
However, note that a general reset sets
the range to the 0 %FS value of the
input 1 range.
10
C
1
0
SP1 upper limit
100 %FS
Lower limit to 9999 U
[Note]
Changing the input 1 range has no
effect on the range.
However, note that a general reset sets
the range to the 0 %FS value of the
input 1 range.