
7-27
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
10
E
D
3
Event 3 standby
0
0: Standby OFF
1: Standby ON
[Note]
The controller stands by after power
is restored and in the READY mode.
When the event type setting is ≥ 50,
“– – – –” is displayed and setting is not
possible.
11
H
Y
S
3
Event 3 hysteresis
5
0 to 200 U (when event type is neither MV
nor MFB)
0.0 to 20.0 % (when event type is MV or
MFB)
[Note]
When the event type setting is ≥ 50,
“– – – –” is displayed and setting is not
possible.
12
D
L
3
Event 3 ON delay
time
0
0 to 3600 s
13
T
T
Time event type
0
0: T1 to T5 are all time events.
1: T1 is a segment No. event.
T2 to T5 are time events.
2: T1 and T2 are segment No. events.
T3 to T5 are time events.
3: T1 to T3 are segment No. events.
T4 and T5 are time events.
4: T1 to T4 are segment No. events.
T5 is a time event.
5: All T1 to T5 are segment No. events.
[Note]
On models not supporting time
events, “– – – –” is displayed and set-
ting is not possible.
Settings can be changed only in the
READY mode.
14 -
Unused
15 -
Unused
16 -
Unused