7-11
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
23
C
Y
.
2
Output 2 time
proportional output
cycle
10
5 to 120 s (relay output)
1 to 60 s (voltage output)
[Note]
On models whose output 2 is neither
relay output nor voltage output,
“– – – –” is displayed and setting is not
possible.
24
C
Y
.
3
Unused
–
[Note]
“– – – –” is displayed and setting is not
possible.
25
d
V
-L
3-position control
deviation lower limit
5 U
0 to 1000 U
[Note]
On models other than 3D output mod-
els, “– – – –” is displayed and setting is
not possible.
26
d
V
-h
3-position control
deviation upper limit
5 U
27
H
Y
-L
3-position control
lower limit hysteresis
5 U
28
H
Y
-H
3-position control
upper limit hysteresis
5 U
29
.-C
Motor control
method selection
0
0: MFB control (conventional) + estimat-
ed position control
1: MFB control (conventional) only
2: Estimated position control only
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
30
.-A
t
Motor valve opening
automatic adjust-
ment
0
0: Adjustment disabled
1: Adjustment enabled
[Note]
On models other than 2G output mod-
els, “– – – –” is displayed and setting is
not possible.
On 2G output models, when
.-C
setting is 2, “– – – –” is displayed and
setting is not possible.