WARNING
Before removing, mounting, or wiring the DCP31, be sure to turn off the power to
the DCP31 and all connected devices.
Failure to do so might cause electric shock.
■
Relay output (0D)
Connect as follows:
Handling Precautions
When switching small currents, connect a bleeder resistor to allow
current flow of the minimum relay switching input (100 mA min.).
■
Current output (5G)
Connect as follows:
Handling Precautions
4 to 20 mAdc and 0 to 20 mAdc can be selected in setup data
C
9
0
.
11
12
13
Load
Power supply
Contact rating, resistive load
5A (30 Vdc/120 Vac)
4A (240 Vac)
Minimum switching current: 100 mA
11
12
13
Actuator
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.
4-9
Chapter 4. WIRING
4 - 8
Connecting control outputs (outputs 1, 2)