External switch (RSW) inputs
In all, the
DCP31
is provided with 12 external switch inputs. Each
of these inputs are differentiated by RSW1, RSW2 and so forth to
RSW12. On models whose option 2 catalog No. is “0”, only inputs
RSW1 to RSW4 are mounted.
(RSW: external switch input)
●
●
External switch input types
The functions of RSW1 to 4, and RSW8 to 12 are fixed.
The functions of RSW5 to 7 are selected by the setup setting.
External
Switch No.
Function
Detection Method
RSW1
RUN
Rising edge
RSW2
HOLD
Rising edge
RSW3
RESET
Rising edge
RSW4
ADV
Rising edge
RSW5
RSW6
RSW7
Selected by setup from the following
functions
FAST
Rising edge
PV start
Rising edge
AUTO/MANUAL
Rising/falling edge
AT start/stop
Rising/falling edge
G.Soak cancel by OR conditions
Status
G.Soak cancel by AND conditions
Status
Direct/reverse action switching
Status
RSW8
Program No. selection Weighting 1
Status
RSW9
Program No. selection Weighting 2
Status
RSW10
Program No. selection Weighting 4
Status
RSW11
Program No. selection Weighting 8
Status
RSW12
Program No. selection Weighting 10
Status
• With PV is valid only in the program operation mode and
READY mode, and the PV start RUN mode is entered regardless
of the PV start setting in the program. Note, however, that RUN
mode is entered from the start point of the selected segment in
READY mode when there is no SP for the PV start.
6-9
Chapter 6. OPERATION
6 - 4
External Switch (RSW) Operations