7-13
Chapter 7. PARAMETER SETUP
• When
L
O
C
is set to 3, the following keys are disabled.
Basic display state:
PROG
(program selection)
(program selection)
RUN/HOLD
(RUN, HOLD)
PROG
+
RUN/HOLD
(RESET)
PROG
+
DISP
(ADV)
FUNC
+
(FAST)
A/M
(AUTO, MANUAL)
AT
(AT start, AT cancel)
FUNC
+
CLR
+
DISP
(general reset)
However, note that MV (when controller functions are selected) and
SP (when programmer functions are selected) can be changed in the
basic display state in the MANUAL mode.
• When
L
O
C
is set to 4, all keys disabled when
L
O
C
is set to 2 and 3
are disabled.
●
●
P
R
T
C
(program protect)
0: Changing program settings enabled
1: Changing program settings disabled
When
P
R
T
C
is set to 1, the following keys are disabled.
Basic display state:
+
PROG
(program copy)
FUNC
+
CLR
+
DISP
(general reset)
Program setup state:
ENT
(start of value entry)
FUNC
+
ENT
(segment insert/delete)
●
●
O
T
L
(MV change limit)
The MV is increased or decreased by the same value so that the
output change is taken as the limit setting value when the output
change (%) after PID operation is greater than this limit setting.
The below example shows the actual change in MV when the MV
changes from 20 % to 22 % with the change limit setting at 0.5 %.
MV is output at 0.5 % setting value increments every 0.1 s, and
reaches 22 % in 0.4s.
%
22
21
20
t
t + 0.1
t + 0.2
t + 0.3
t + 0.4
s