![Azbil DCP31 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/azbil/dcp31/dcp31_user-manual_3042607034.webp)
■
Inputs
●
●
Thermocouple
Input Format
Range No.
Code
Temp. Range (°C)
Temp. Range (°F)
K (CA)
0
K09
0 to 1200
0 to 2400
K (CA)
1
K08
0.0 to 800.0
0 to 1600
K (CA)
2
K04
0.0 to 400.0
0 to 750
K (CA)
3
K29
-200 to +1200
-300 to +2400
K (CA)
4
K44
-200.0 to +300.0
-300 to +700
K (CA)
5
K46
-200.0 to +200.0
-300 to +400
E (CRC)
6
E08
0.0 to 800.0
0 to 1800
J (IC)
7
J08
0.0 to 800.0
0 to 1600
T (CC)
8
T44
-200.0 to +300.0
-300 to +700
B (PR30-6)
9
B18
0 to 1800
0 to 3300
R (PR13)
10
R16
0 to 1600
0 to 3100
S (PR10)
11
S16
0 to 1600
0 to 3100
W (WRe5-26)
12
W23
0 to 2300
o to 4200
W (WRe5-26)
13
W14
0 to 1400
0 to 2552
PR40-20
14
D19
0 to 1900
0 to 3400
Ni-Ni-Mo
15
Z13
0 to 1300
32 to 2372
N
16
U13
0 to 1300
32 to 2372
PL II
17
Y13
0 to 1300
32 to 2372
DIN U
18
Z08
-200.0 to +400.0
-300 to +750
DIN L
19
Z07
-200.0 to +800.0
-300 to +1600
Golden iron chromel
20
Z06
0.0 to +300.0K
—
2-10
Chapter 2. NAMES & FUNCTIONS OF PARTS
2 - 3
Input Type and Range No.