5-4
Chapter 5. FUNCTIONS
• Segment progression
- Output is OFF until the program progresses to the segment
containing the event setting.
- When the program progresses to the segment containing the
event setting, event ON/OFF operation is carried out according
to the event setting value.
- The previous setting is valid until the program progresses to a
segment containing a new event setting.
For this reason, set as follows to disable the event set in the
previous segment from a certain segment onwards:
Direct action events: Upper limit value of event setting
Reverse action events: Lower limit value of event setting
Note, however, that some types of event turn ON even if events
are set as shown above.
- When the program has progressed to the No.1 segment by
the cycle or pattern link functions, the previous setting is
disabled. Output is OFF unless the No.1 segment contains an
event setting.
• Other
On 5G output models, when setup data
C
1
8
is set to 1, and SP
output (programmer functions) is selected, the MV direct/reverse
event does not function.