7-21
Chapter 7. PARAMETER SETUP
matic re-adjustment has ended successfully or when the power
has been reset.
- Fully closed count - fully open count < 500
- Fully closed count > fully open count
- Time from fully closed to fully open is less than 5 s
- MFB disconnected alarm (
A
L
1
0
,
A
L
1
1
) occurs continu-
ously or frequently
- The time taken for the MFB count to stabilize exceeds 5 min
- Faulty wiring of MFB or switching relay
(However, note that all faulty wiring cannot be detected as
an error.)
●
●
.-t
(motor valve opening adjustment fully open/closed time)
When
.-C
is set to 2, the set time is taken as the base for all opera-
tions. Enter the time correctly in 0.1 s units.