7-64
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
21
T
-B
.
a
Input linearization table
approximation B10
1000 U
22
T
-B
.
B
Input linearization table
approximation B11
1000 U
■
Description of table data settings
●
●
t
-A
.
1
to
t
-A
.
b
●
●
t
-b
.
1
to
t
-b
.
b
• These settings are for the A-axis (input) and B-axis (output) set-
tings of input 1 linearization table approximation.
• Both ends of the linearization table are fixed at -2000 U, -2000 U
and 10000 U,10000 U.
The linearization table is formed by connecting 11 points of table
data settings between the two ends.
• Table data is set not by percentages but directly by engineering
unit. When the range type is set to linear, set scaled values.
1
2
3
4
5
6
7
9
8
10 11
B-axis (output)
Fixed value
(10000, 10000)
A-axis (input)
Fixed value
(-2000, -2000)