7-51
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
68
C
6
8
Programming item:
Events 1 to 3
0
0: Display ON
1: Display OFF
[Note]
Even if each of the items is set to 1, the
function operates if program data is
set.
On models not supporting time
events, time event items are not dis-
played in program settings regardless
of the number of
C
6
9
settings.
69
C
6
9
Programming item:
Time events 1 to 5
0
70
C
7
0
Programming item:
PID set, G.Soak
0
71
C
7
1
Programming item:
PV start, cycle, pat-
tern link
0
72
C
7
2
Cold junction com-
pensation
0
0: Compensated internally
1: Compensated externally
[Note]
When the input 1 range type is other
than a thermocouple, “– – – –” is dis-
played and setting is not possible.
73
C
7
3
Input operation at
input 1 disconnec-
tion
0
0: Upscale
1: Downscale
[Note]
This setting is valid when the input 1
range type is thermocouple, resistance
temperature detector or linear (mV
series).
74
C
7
4
Voltage timepropor-
tional output system
0
0: Input ON again enabled within time-
proportional cycle
1: Input ON again disabled within time-
proportional cycle
[Note]
When both of outputs 1 and 2 are not
voltage timeproportional outputs, “–
– – –” is displayed and setting is not
possible.
75
C
7
5
Output 1 selection
Not fixed
0: Current output
1: Voltage output
[Note]
When each of the outputs are relay
output, positionproportional out-
put, auxiliary output or output is not
mounted, “– – – –” is displayed and
setting is not possible.
Factory setting is 1 if outputs are volt-
age output according to output type.
Otherwise, the setting is 0.
76
C
7
6
Output 2 selection
Not fixed