7-57
Chapter 7. PARAMETER SETUP
●
●
C
7
8
(voltage output 1 adjustment)
●
●
C
7
9
(voltage output 2 adjustment)
[Constant current type]
• Input current (maximum):
Check that the input current is within the maximum allow-
able current or less, then the parallel connection can be made.
• Operating voltage range (input):
Check that the voltage between the terminals of the voltage
pulse output is within the specified range.
This example shows the calculation for the connection of this unit
and the PGM10N015.
(Note: For connection with other model number, check the specifi-
cations of each model.)
• Input current:
Since the input current is 10 mA or less, up to two units
(10 mA × 2 = 20 mA < 22 mA [maximum allowable current])
can be connected in parallel.
• Operating voltage range (input):
The rated voltage is DC 3.5 to 30 V, so an open terminal volt-
age of 25 V or less is within range.
Connection diagram
Example: Number of connectable units and settings
Settings
SSR to be used
6D model
5K model
C78
C79
C78
C79
PGM10N
1 unit
10 or more
disable
10 or more 10 or more
2 units (parallel)* 20 or more
disable
20 or more 20 or more
PGM10F
1 unit
12 or more
disable
12 or more 12 or more
* : It is able to connect 2 units for each heat side (setup item C78) and cool side
(setup item C79), because the 5K model has heat/cool control output. Using an
SSR in the 5K model, set the setup of C75 and C76 to 1(voltage output).
This unit
+
–
PGM10N
+
–
+
–
PGM10N