Note
“U” and “%FS” used in the “Factory Setting” and “Setting” columns in
the table mean the following:
U:
The decimal point changes according to the input range type
setting. For example, when one digit past the decimal point is
allowed, -1999 U becomes 199.9, and 9999 U becomes 999.9.
%FS: The numbers and decimal point position changes according to
the input range setting.
For example, when the input range is 0.0 to 800.0°C, 0 %FS is 0.0
and 100 %FS is 800.0.
■
Variable parameter settings “
P
A
R
A
”
No. Item Code
Item
Factory
Setting
User
Setting
Setting
1
L
O
C
Key lock
0
0: Key lock disabled
1: Display of setup data settings disabled
2: Display of parameter settings and
program settings disabled
3: Use of operation keys disabled
4: Display of parameter settings and
program settings displayed, and use of
operation keys disabled
[Note]
Two or more key lock setting values
for actual key lock items and items
assigned to
PARA
can be displayed and
set.
2
P
R
T
C
Program protect
0
0: Changing program settings enabled
1: Changing program settings disabled
3
F
L
Input 1 digital filter
0.0
0.0 to 120.0 s
[Note]
0.0 disables the filter.
4
P
B
1
Input 1 bias
0 U
-1000 to +1000 U
5
S
B
1
SP1 bias
0 U
-1999 to +9999 U
[Note]
SP bias is commonly effective in all
programs and all segments.
6
O
T
L
MV change limitter
(CH1)
0.0
0.0 to 10.0 % (0.1 %s steps)
[Note]
0.0 disables the limit.
7-8
Chapter 7. PARAMETER SETUP
7 - 3
Parameter Setup List