5-7
Chapter 5. FUNCTIONS
When the event type is set to PV range alarm, the event turns ON
if any one of the alarms in the PV range alarm group occurs.
When the event type is set to controller alarm, the event turns ON
if any one of the alarms in the controller alarm group occurs.
• ADV
This is ON for 1s after executing program advance. The event ON
delay is disabled and a delay is not applied.
• Program end
When the
DCP31
automatically (including ADV) reaches the
READY mode from program operation status (RUN, HOLD,
FAST) without performing RESET operation, the event is turned
ON. When shifting from END mode to READY mode, the event
is not turned ON as RESET operation is required.
This event is cancelled (ON→OFF) when one of the following
conditions is satisfied:
• When RESET operation is performed.
• When shifting from READY to RUN mode.
• When power is again supplied.