Item
Specification
Program
Number of programs
19
Number of segments
30 per program
Segment setting system RAMP-X system: Set by set points (SP) and time.
Segment time
0 to 99 h 59 min, 0 to 99 min 59s, or 0.0 to 599.9 s (time unit selectable)
Basic time accuracy
±0.01 % (0.1 s delay when segment time setting=0)
Events (3)
Set operating point.
Time events (5)
Set ON and OFF times.
PID set No.
Set 0 to 8 (Set 0 for continuation of previous segment) (Set 0 to 4 on
heat/cool models.)
G.Soak
Sets G.Soak width 0 to 1000 U.
PV start
Sets program ON/OFF.
Cycle
Sets program count 0 to 9999.
Pattern link
Sets program No.0 to 19 (0: no link)
Tag
Sets 8 alphanumerics for each program (not displayed on controller)
Input
Input type
Thermocouple: K, E, J, T, B, R, S (JIS C 1602-1981)
WRe5-26 (Hoskins Data)
PR40-20 (Johnson Matthey Data)
Ni·NiMo (General electric Data)
N (N.B.S. Monograph 161)
PLII (Engelhard Industries Data (IPTS68))
DIN U, DIN L (DIN 43710-1985)
Gold iron chromel (Hayashidenko Data)
Resistance temperature detector (RTD):
Pt100, JPt100 (JIS C 1604-1989)
DC current:
4 to 20 mA, 0 to 20 mA, 0 to 10 mA
DC voltage:
−10 to +10 mV, 0 to 100 mV, 0 to 1 V, −1 to +1 V, 1 to 5 V,
0 to 5 V, 0 to 10 V
Multi-range of thermocouple, resistance temperature detector,
DC voltage, and DC current (see page 2-8, 2-9).
Input readout accuracy
±0.1 %FS ±1 U (varies according to standard conditions, display value
conversion and range)
•
For the K44, K46, and T44 thermocouples at –100 °C and colder:
±1 °C±1 U
•
At 260 °C max. of B thermocouple:
±4 %FS ±1 U
At 260 to 800 °C:
±0.4 %FS ±1 U
At 800 to 1800 °C:
±0.2 %FS ±1 U
•
At 100 °C max. of R and S thermocouples: ±0.2 %FS ±1 U
At 100 to 1600 °C:
±0.15 %FS ±1 U
•
At 300 °C max. of PR40-20 thermocouple: ±2.5 %FS ±1 U
At 300 to 800 °C:
±1.5 %FS ±1 U
At 800 to 1900 °C:
±0.5 %FS ±1 U
•
Golden iron chromel thermocouple:
±1.5 K ±1 U
•
Range of F01, F33, F38, P01, P33 and P38 of RTD input: ±0.15 %FS ±1 U
•
At 0 to 10 mV range:
±0.15 %FS ±1 U
•
At −100 °C max. of DIN U thermocouple: ±2 °C ±1 U
At −100 to 0 °C:
±1 °C ±1 U
•
At −100 °C max. of DIN L thermocouple: ±1.5 °C ±1 U
11-1
Chapter 11. SPECIFICATIONS
11 - 1
Specifications