11-5
Chapter 11. SPECIFICATIONS
Item
Specification
Control
Auxiliary output
Type
PV, SP, deviation, MV, MFB
Scaling
Supported
Output resolution
1/10000
Output
0D output 1
3D outputs 1, 2
Relay contact
output
Contact type:
1a1b
Contact rating:
5 A (24 Vdc, resistive load)
5 A (120 Vac, resistive load)
4 A (240 Vdc, resistive load)
Allowable contact voltage:
250 Vac, resistive load
125 Vdc, resistive load
Max. switching power:
150 W, resistive load
960 VA, resistive load
Life:
100,000 operations
(resistive load at contact
rating, frequency: 30
operations/minute)
Min. switching voltage: 5 V
Min. switching current: 100 mA
Output resolution:
1/1000
Time-proportional cycle: 5 to 120 s
2G output 1
M/M drive relay
Contact type:
1 a (2 circuits)
Contact rating:
2.5 A (30 Vdc, L/R=0.7 ms)
4 A (120 Vac, cosø=0.4)
2 A (240 Vac, cosø=0.4)
Allowable contact voltage:
250 Vac, cosø=0.4
125 Vdc, L/R=0.7 ms
Max. switching power:
75 W (L/R=0.7 ms)
480 VA (cosø=0.4)
Life:
100,000 operations
(cosø=0.4 at contact
rating, frequency: 30
operations/minute)
Min. switching voltage: 5 V
Min. switching current: 100 mA
MFB (motor feedback) input range:
100 to 2500 Ω
Control at MFB (motor feedback) disconnection:
ON/OFF for continuation
of operation according to
MFB estimated position
can be selected.