7-49
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
50
C
5
0
Auxiliary output 2
lower limit (4 mA)
0
-1999 to +9999 U
-199.9 to +999.9 %
[Note]
When the auxiliary output type is MV
or MFB, the unit is %. Otherwise, the
unit is U.
51
C
5
1
Auxiliary output 2
lower limit (20 mA)
1000
52
C
5
2
External switch input
RSW5 assignment
0
0: NOP
1: Fast operation
2: PV start
3: NOP
4: AT start/stop
5: NOP
6: Manual/auto operation
7: Cancel G.Soak by OR conditions
8: Cancel G.Soak by AND conditions
9: Direct/reverse action inversion
10 to 20: NOP
[Note]
On external switch 4-input models, “–
– – –” is displayed and setting is not
displayed.
When the same assignment is set to
two or more RSWs, the RSW setting
with the lowest No. is valid.
When this setting is set to NOP, the
controller state is not switched by
external switch input ON/OFF. The
controller state can be switched ON/
OFF by communications.
53
C
5
3
External switch input
RSW6 assignment
0
54
C
5
4
External switch input
RSW7 assignment
0