4-18
Chapter 4. WIRING
●
●
5-lead RS-485 mutual connection
Handling Precautions
• Be sure to connect SG termi-
nals each other.
Failure to do so might cause
unstable communications.
Connect terminating resistors (150 Ω ±5 %, 1/2 W min.) to both ends of the transmis-
sion line.
Grounding of the shielded FG terminal should be carried out at only one end and not
both ends.
57