7-55
Chapter 7. PARAMETER SETUP
●
●
C
4
7
(auxiliary output 1 lower limit)
●
●
C
4
8
(auxiliary output 1 upper limit)
●
●
C
5
0
(auxiliary output 2 lower limit)
●
●
C
5
1
(auxiliary output 2 upper limit)
• This is the scaling setting for auxiliary output. The values of the
upper limit setting and lower limit setting can also be inverted.
• In the following example, the type is set to MV at auxiliary input
1. 12 mA is output when MV is 100 % and 20 mA is output when
MV is 0%. In the following figure, MV is 200 % when virtually
calculated at 4 mA.
Accordingly, the setting of
C
4
7
and
C
4
8
become 200.0 and 0.0,
respectively.
●
●
C
6
5
(time display)
0: Remaining segment time
1: Total operation time
• This selects the time display in the basic display state in the pro-
gram operation mode.
• When set to 0, in the READY mode, the time setting value of the
currently selected segment is displayed.
• When set to 0, in the RUN, HOLD, FAST or END modes, the
remaining time for the currently executing segment is displayed
after being rounded down.
For example, if the remaining time is 1h, 30 min, 59 s when the
time unit is set to “h: min”, the time display is “
1
.3
0
”.
• When set to 1, in the READY mode, the time display is “
0
.0
0
”.
• When set to 1, in the RUN, HOLD, FAST or END modes, the time
it takes to shift from the READY to the RUN mode is displayed
after being round down. Also, after “
9
9
.5
9
” the time display
changes to “
0
.0
0
”.
For example, if the remaining time is 101 h, 30 min, 59 s when the
total operation time is set to “h: min”, the time display is “
1
.3
0
”.
• In the FAST mode, the time display changes according to the
FAST scale if this parameter is set to either 0 or 1.
MV
4 mA
12 mA
20 mA
200 %
100 %
Auxiliary output 1