8-19
Chapter 8. PROGRAM SETUP
●
●
Display (inserting segment)
●
●
Display (deleting segment)
• When you insert a segment, a new segment is automatically cre-
ated at the currently displayed segment No., and all segment Nos.
onward are incremented by one. The setting of the inserted seg-
ment is as follows:
SP setting value: Same value as original segment before the new
segment was in serted
Time setting value: 0:10
Events, time events and G.Soak are not set, and the PID set No. is
set to 0.
• If you try to insert a segment in a program already containing 30
segments, pressing
ENT
will not insert the segment.
• When you delete a segment, the next segment shifts down to the
currently displayed segment No. and subsequent segment Nos. are
decremented by one.
When you delete the last segment, the display changes to “- - - -”
indicating that nothing is set.
• Segments cannot be inserted or deleted from currently running
(RUN, HOLD, FAST, END) programs.