7-52
Chapter 7. PARAMETER SETUP
No. Item Code
Item
Factory
Setting
User
Setting
Setting
77
C
7
7
Unused
–
[Note]
“– – – –” is displayed and setting is not
possible.
78
C
7
8
Voltage output 1
adjustment
15
2 to 22 mA
[Note]
When each of the outputs are other
than voltage output, “– – – –” is dis-
played and setting is not possible.
Normally, use the factory setting.
79
C
7
9
Voltage output 2
adjustment
15
80
C
8
0
Unused
–
[Note]
“– – – –” is displayed and setting is not
possible.
81
C
8
1
Input 1 burnout
current (expansion
setting 1)
0
0: Burnout current ON
1: Burnout current OFF
[Note]
Normally set to 0.
Set to 1 when infra-red thermocouple
RT50 is connected to input 1.
82
C
8
2
Expansion setting 2
0
0: Expansion disabled
1: Expansion enabled
[Note]
This setting is for service use only.
83
C
8
3
Unused
–
[Note]
“– – – –” is displayed and setting is not
possible.
84
C
8
4
Station address
0
0 to 127
[Note]
On models not supporting commu-
nications, “– – – –” is displayed and
setting is not possible.
0 disables communication.
85
C
8
5
Transmission rate/
Character format
0
0: 9600 bps/even parity, 1 stop bit
1: 9600 bps/no parity, 2 stop bits
2: 4800 bps/even parity, 1 stop bit
3: 4800 bps/no parity, 2 stop bits
[Note]
On models not supporting commu-
nications, “– – – –” is displayed and
setting is not possible.