196 Parameters
00:00:00
00 00:00
0111 1000
0000b
00:00:00
00 00:00
Defines the start date of season 1 in format dd.mm, where dd
is the number of the day and mm is the number of the month.
The season changes at midnight. One season can be active
at a time. Timers are started on exception days even if they
are not inside the active season.
The season start dates (1…4) must be given in increasing
order to use all seasons. The default value is interpreted that
the season is not configured. If the season start dates are not
in increasing order and the value is something else than the
default value, a season configuration warning is given.
01.01.
01.01…31.12
Season start date.
Defines the start date of season 2.
See
01.01.
Defines the start date of season 3.
See
01.01.
Defines the start date of season 4.
See
01.01.
Defines how many of the exceptions are active by specifying
the last active one. All preceding exceptions are active.
Exceptions 1…3 are periods (duration can be defined) and
exceptions 4…16 are days (duration is always 24 hours).
Example:
If the value is 4, exceptions 1…4 are active, and
exceptions 5…16 are not active.
3
0…16
Number of active exception periods or days.
-
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...