46 Program features
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V) or current (0/4…20 mA) input with
parameters. Each input can be filtered, inverted and scaled.
Settings
Parameter group
(page
).
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Analog output 1 can be
set as a voltage (0/2…10 V) or current (0/4…20 mA) output with a parameter. Analog
output 2 always uses current. Each output can be filtered, inverted and scaled.
Settings
Parameter group
(page
Programmable digital inputs and outputs
The control unit has six digital inputs.
Digital input DI5 can be used as a frequency input.
Digital input DI6 can used as a thermistor input.
Six digital inputs can be added by using a CHDI-01 115/230 V digital input extension
module and one digital output by using a CMOD-01 multifunction extension module.
Settings
Parameter groups
(page
) and
(page
Programmable frequency input and output
Digital input DI5 can be configured as a frequency input.
A frequency output can be implemented with a CMOD-01 multifunction extension
module.
Settings
Parameter groups
(page
) and
(page
) and
(page
).
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...