324 Additional parameter data
45.12 Energy tariff 1
0.000…4294966.296
(defina-
ble)
1000 = 1
currency unit
45.13 Energy tariff 2
0.000…4294966.296
(defina-
ble)
1000 = 1
currency unit
45.14 Tariff selection
-
-
1 = 1
45.18 CO2 conversion factor
0.000…65.535
tn/ MWh
1000 = 1
tn/MWh
45.19 Comparison power
0.00…10000000.00
kW
10 = 1 kW
45.21 Energy calculations reset
0…1
-
1 = 1
45.24 Hourly peak power value
-3000.00 … 3000.00
kW
1 = 1 kW
45.25 Hourly peak power time
N/A
45.26 Hourly total energy (resettable)
-3000.00 … 3000.00
kWh
1 = 1 kWh
45.27 Daily peak power value
(resettable)
-3000.00 … 3000.00
kW
1 = 1 kW
45.28 Daily peak power time
N/A
45.29 Daily total energy (resettable)
-30000.00 … 30000.00
kWh
1 = 1 kWh
45.30 Last day total energy
-30000.00 … 30000.00
kWh
1 = 1 kWh
45.31 Monthly peak power value
(resettable)
-3000.00 … 3000.00
kW
1 = 1 kW
45.32 Monthly peak power date
N/A
45.33 Monthly peak power time
N/A
45.34 Monthly total energy
(resettable)
-1000000.00 … 1000000.00
kWh
1 = 1 kWh
45.35 Last month total energy
-1000000.00 … 1000000.00
kWh
1 = 1 kWh
45.36 Lifetime peak power value
-3000.00 … 3000.00
kW
1 = 1 kW
45.37 Lifetime peak power date
N/A
45.38 Lifetime peak power time
N/A
46 Monitoring/scaling settings
46.01 Speed scaling
0.00…30000.00
rpm
100 = 1 rpm
46.02 Frequency scaling
0.10…1000.00
Hz
100 = 1 Hz
46.03 Torque scaling
0.1…1000.0
%
10 = 1%
46.04 Power scaling
0.10…30000.00 kW or
0.10…40200.00 hp
kW or hp
10 = 1 unit
46.05 Current scaling
0…30000
A
1 = 1 A
46.06 Speed ref zero scaling
0.00 … 30000.00
rpm
100 = 1 rpm
46.11 Filter time motor speed
2…20000
ms
1 = 1 ms
46.12 Filter time output frequency
2…20000
ms
1 = 1 ms
46.13 Filter time motor torque
2…20000
ms
1 = 1 ms
46.14 Filter time power
2…20000
ms
1 = 1 ms
46.21 At speed hysteresis
0.00…30000.00
rpm
100 = 1 rpm
46.22 At frequency hysteresis
0.00…1000.00
Hz
100 = 1 Hz
46.31 Above speed limit
0.00…30000.00
rpm
100 = 1 rpm
46.32 Above frequency limit
0.00…1000.00
Hz
100 = 1 Hz
No.
Name
Type
Range
Unit
FbEq32
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...