Parameters 291
98
Motor values supplied by the user that are used in the motor
model.
These parameters are useful for non-standard motors, or to
just get more accurate motor control of the motor on site. A
better motor model always improves the shaft performance.
Activates the motor model parameters
and
Notes
:
• Parameter value is automatically set to zero when ID run is
. The values
of parameters
are then updated according to
the motor characteristics identified during the ID run.
• Measurements made directly from the motor terminals
during the ID run are likely to produce slightly different
values than those on a data sheet from a motor
manufacturer.
• This parameter cannot be changed while the drive is
running.
Not selected
…
inactive.
0
Motor parameters
…
are used as the
motor model.
1
Defines the stator resistance
R
S
of the motor model.
With a star-connected motor,
R
S
is the resistance of one
winding. With a delta-connected motor,
R
S
is one-third of the
resistance of one winding.
0.00000 p.u.
0.00000…0.50000
p.u.
Stator resistance in per unit.
-
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000…0.50000
p.u.
Rotor resistance in per unit.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000…10.00000
p.u.
Main inductance in per unit.
-
Defines the leakage inductance
σ
L
S
.
Note:
This parameter is valid only for asynchronous motors.
0.00000 p.u.
0.00000…1.00000
p.u.
Leakage inductance in per unit.
-
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000…10.00000
p.u
Direct axis inductance in per unit.
-
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000…10.00000
p.u
Quadrature axis inductance in per unit.
-
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...