398 Fieldbus control through a fieldbus adapter
Contents of the fieldbus Status word
The upper case boldface text refers to the states shown in the state diagram (page
.
Bit
Name
Value STATE/Description
0
Ready to switch
ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
Ready run
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
2
Ready ref
1
OPERATION D
.
0
OPERATION INHIBITED
.
3
Tripped
1
FAULT
.
0
No fault.
4
Off 2 inactive
1
OFF2 inactive.
0
OFF2 ACTIVE
.
5
Off 3 inactive
1
OFF3 inactive.
0
OFF3 ACTIVE
.
6
Switch-on inhibited 1
SWITCH-ON INHIBITED
.
0
–
7
Warning
1
Warning active.
0
No warning active.
8
At setpoint
1
OPERATING
. Actual value equals reference = is within tolerance
).
0
Actual value differs from reference = is outside tolerance limits.
9
Remote
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
10
Above limit
-
See bit 10 of
11
User bit 0
-
See parameter
12
User bit 1
-
See parameter
.
13
User bit 2
-
See parameter
.
14
User bit 3
-
See parameter
.
15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...