112 Parameters
Drive status word 1.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 1.
1 = 1
Drive status word 2.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 2.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Enabled
1 = If Run permissive (par.
) and start interlock signals (par.
) signals are all present.
Note:
This bit is not affected by the presence of a fault.
1
Inhibited
1 = Start inhibited. To start the drive, the inhibiting signal (see par.
) must be removed and the start signal cycled.
2
DC charged
1 = DC circuit has been charged
3
Ready to start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control
1 = Drive is in local control
9
Network control
(see page
10
Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12
Reserved
13
Start request
1 = If Start requested. 0 = When Run permissive signal (see par.
) is 0.
14…15 Reserved
Bit
Name
Description
0
Identification run done 1 = Motor identification (ID) run has been performed
1
Magnetized
1 = The motor has been magnetized
2
Reserved
3
Speed control
1 = Speed control mode active
4
Reserved
5
Safe reference active 1 = A “safe” reference is applied by functions such as
parameters
6
Last speed active
1 = A “last speed” reference is applied by functions such as
parameters
7
Loss of reference
1 = Reference signal lost
8
Emergency stop failed 1 = Emergency stop failed (see parameters
)
9…12
Reserved
13
Start delay active
1 = Start delay (par.
) active.
14…15 Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...